OHA Drinking Water Services
PWS ID:
00079 ---- BAY CITY WATER SYSTEM
GW/GWUDI Source Detail
Non-purchased Groundwater/GWUDI Sources:
Contact Us:
- Email us with questions, comments,
or suggestions about this page.
SRC-AA: 1975 WELL #1
GW, Active, Permanent ---- Operating Period: Jan 1 - Dec 31
Disinfection: GWR 4-LOG VIRUS COMPLIANCE MON; HYPOCHLORINATION, POST
Sensitivity Analysis Data
Aquifer sensitivity: |
High |
|
Surface water within 500 feet: |
Yes |
Construction adequate?: |
No - Seal Not Constructed Properly |
|
Surface water type: |
Stream |
E. coli sources within 2-year time-of-travel: |
Yes |
|
Data last updated: |
01/11/2024 |
Monthly Assessment Monitoring Data
Monthly Assessment Monitoring Required? Complete
Monthly Schedule (Closed): 1 sample(s) per month to be taken beginning 05/01/2011 - 01/31/2012
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total |
# Samples
TC+
E. coli+ | 1 1
1 | 0 - - | 0 - - | 0 - - | 1 0
0 | 1 0
0 | 1 0
0 | 0 - - | 1 0
0 | 1 0
0 | 1 0
0 | 1 0
0 | 8 1
1 |
Outcome/Determination: Low Risk |
No historic GWUDI data were found.
SRC-AB: 1980 WELL #2
GW, Active, Permanent ---- Operating Period: Jan 1 - Dec 31
Disinfection: GWR 4-LOG VIRUS COMPLIANCE MON; HYPOCHLORINATION, POST
Sensitivity Analysis Data
Aquifer sensitivity: |
High |
|
Surface water within 500 feet: |
Yes |
Construction adequate?: |
No - Seal Not Constructed Properly |
|
Surface water type: |
Stream |
E. coli sources within 2-year time-of-travel: |
Yes |
|
Data last updated: |
01/11/2024 |
Monthly Assessment Monitoring Data
Monthly Assessment Monitoring Required? Complete
Monthly Schedule (Closed): 1 sample(s) per month to be taken beginning 05/01/2011 - 01/31/2012
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total |
# Samples
TC+
E. coli+ | 1 1
1 | 0 - - | 0 - - | 0 - - | 1 0
0 | 1 0
0 | 1 0
0 | 0 - - | 1 1
0 | 1 0
0 | 1 0
0 | 1 0
0 | 8 2
1 |
Outcome/Determination: Low Risk |
No historic GWUDI data were found.
SRC-AC: 2023 WELL #3
GW, Active, Permanent ---- Operating Period Unknown
Disinfection: GWR 4-LOG VIRUS COMPLIANCE MON; HYPOCHLORINATION, POST
Sensitivity Analysis Data
Aquifer sensitivity: |
High |
|
Surface water within 500 feet: |
Yes |
Construction adequate?: |
Yes |
|
Surface water type: |
Stream |
E. coli sources within 2-year time-of-travel: |
Yes |
|
Data last updated: |
02/02/2024 |
Monthly Assessment Monitoring Data
Monthly Assessment Monitoring Required? No
No monthly assessment monitoring schedule found.
No historic GWUDI data were found.