PWS ID: 06024 ---- CONDON HEIGHTS WS

Lead and Copper Compliance Actions
  • No lead and copper schedules found.


  • Action Levels:  Lead = 0.015 mg/L;  Copper = 1.3 mg/L All detailed results
    Lead and Copper 90th Percentile Summary Results and Consumer Notices*
    Sample Dates Date Received Sample Count Duration Lead (mg/L) Copper (mg/L) Consumer
    Notice Date*
    Sep 23, 2019 - Sep 24, 2019Oct 08, 201953Y 0.0005 0.0502
    Aug 03, 2016 - Aug 03, 2016Aug 15, 201653Y 0.0009 0.0785
    Jun 05, 2013 - Jun 05, 2013Jun 11, 201356M 0.0007 0.0495
    Dec 05, 2012 - Dec 05, 2012Dec 18, 201256M 0.0004 0.0329
    Jun 27, 2012 - Jun 27, 2012Jul 09, 201256M 0.0004 0.0475
    Dec 02, 2011 - Dec 02, 2011Dec 13, 201156M 0.0010 0.0364
    Jun 06, 2011 - Jun 06, 2011Jul 07, 201156M 0.0003 0.0120
    *Consumer notice date is the date water customers were notified of their tap results. Consumer notice records are not available prior to 2016.



    For further information on this public water system, click on the area of interest below:
    System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
    Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
    Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
    Chemical Schedule Summary :: Chemical Schedule Details
    Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
    DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA