| Most Recent Water System Survey | |||||||||||||
| Survey date: | Nov 06, 2025 | ||||||||||||
| Notification date: | Dec 17, 2025 (41 days) | ||||||||||||
| Regulating agency: | DWS (REGION 1) | ||||||||||||
| Survey frequency: | 3 YR - Visit the Water System Surveys page to see the list of surveys due each year. | ||||||||||||
| Significant deficiencies and unmet rule requirements: |
Bold text indicates a significant deficiency. All others are unmet rule requirements. * A corrective action plan has been submitted for this significant deficiency or unmet rule requirement. |
||||||||||||
| Water System Site Visit History | ||||||
| Reason | Visit date | Frequency | Next due | Notification date (Days after survey) |
Responsible agency |
Comments and significant deficiencies or unmet rule requirements |
|---|---|---|---|---|---|---|
| Sanitary Survey, Finished (SNSV) | 11/06/2025 | 3 YR | * | 12/17/2025 (41) | REGION 1 | Show details |
| Sanitary Survey, Finished (SNSV) | 02/10/2022 | 3 YR | * | 03/18/2022 (36) | DWP | No details |
| Water Treatment Plant Site Visit (TRTP) | 02/10/2022 | 3 YR | 02/10/2025 | 03/18/2022 (36) | DWP | No details |
| Sanitary Survey, Finished (SNSV) | 04/23/2019 | 3 YR | * | 05/29/2019 (36) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 04/23/2019 | 3 YR | 04/23/2022 | 05/29/2019 (36) | REGION 1 | No details |
| Sanitary Survey, Finished (SNSV) | 09/19/2016 | 3 YR | * | 12/16/2016 (88) | REGION 1 | Show details |
| Water Treatment Plant Site Visit (TRTP) | 09/19/2016 | 3 YR | 09/19/2019 | 12/16/2016 (88) | REGION 1 | No details |
| Sanitary Survey, Finished (SNSV) | 07/18/2013 | 3 YR | * | 07/30/2013 (12) | DWP | Show details |
| Water Treatment Plant Site Visit (TRTP) | 07/18/2013 | 3 YR | 07/18/2016 | 07/30/2013 (12) | DWP | No details |
| Water Treatment Plant Site Visit (TRTP) | 10/21/2011 | 3 YR | 10/21/2014 | 11/07/2011 (17) | DWP | No details |
| Sanitary Survey, Finished (SNSV) | 04/13/2010 | 1 YR | * | 06/14/2010 (62) | DWP | Show details |
| Sanitary Survey, Finished (SNSV) | 04/27/2007 | 3 YR | * | 06/07/2007 (41) | REGION 1 | No details |
| Water Treatment Plant Site Visit (TRTP) | 12/08/2005 | 12/08/2005 (0) | REGION 1 | Hide details | ||
| Comments: The deficiencies noted are as follows: 1. Install a combined filter effluent (CFE) turbidimeter. 2. Profile each filter quarterly (see example provided) and save the data in your files. 3. Assure all the turbidimeters are calibrated quarterly. 4. Calculate CT correctly. a. Measure pH, temperature & chlorine concentration post-reservoirs b. Have circuit rider assist with performing tracer study 5. Develop decision-making protocols for all operators. In addition, I have the following comments: · Monitor alkalinity in the raw water more regularly. We recommend at least weekly testing. · Make sure to maintain valid calibration standards for your turbidimeters. | ||||||
| Sanitary Survey, Finished (SNSV) | 01/15/2003 | 3 YR | * | DWP | Show details | |