OHA Drinking Water Services
OR41
PWS ID: 01139 ---- MIDLAND WATER ASSOCIATION

Most Recent Water System Survey
Survey date: Nov 27, 2025
Notification date: Jan 12, 2026 (46 days)
Regulating agency: DWS (REGION 1)
Survey frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Significant deficiencies and unmet rule requirements:
Category Significant deficiency or unmet rule requirement Due date Resolved date
Surface Water Treatment Turbidity standards not metSep 01, 2026 *
Disinfection Chlorine not measured & recordedMar 02, 2026 Dec 01, 2025
Disinfection No means to adequately determine disinfection contact time under peak flow and minimum storage conditionsMar 02, 2026 Dec 01, 2025
Bold text indicates a significant deficiency. All others are unmet rule requirements.
* A corrective action plan has been submitted for this significant deficiency or unmet rule requirement.


 Hide Site Visit History
Water System Site Visit History
Reason Visit date Frequency Next due Notification date
(Days after survey)
Responsible
agency
Comments and
significant deficiencies or unmet rule requirements
Sanitary Survey, Finished (SNSV) 11/27/2025 3 YR  * 01/12/2026 (46) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 03/24/2022 3 YR  * 05/16/2022 (53) DWP Show details
Water Treatment Plant Site Visit (TRTP) 03/24/2022 6 MN 09/24/2022 05/16/2022 (53) DWP No details
Sanitary Survey, Finished (SNSV) 09/14/2017 3 YR  * 10/06/2017 (22) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 09/14/2017 1 YR 09/14/2018 10/06/2017 (22) REGION 1 No details
Comprehensive Performance Evaluation (CPE) (CPEV) 01/14/2015 03/12/2015 (57) DWP Show details
Sanitary Survey, Finished (SNSV) 05/30/2014 3 YR  * 06/16/2014 (17) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 05/30/2014 1 YR 05/30/2015 06/16/2014 (17) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 11/30/2011 3 YR  * 12/12/2011 (12) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 11/30/2011 6 MN 05/30/2012 12/12/2011 (12) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 03/24/2011 6 MN 09/24/2011 04/08/2011 (15) REGION 1 Hide details
  Comments:
1. Meet all surface water treatment requirements including filter effluent turbidity Maximum Contaminant Levels and disinfection treatment requirements. 2. Ensure that all turbidity, chlorine residual and water quality monitoring (pH and temperature) parameters are measured accurately every day that the treatment plant is in operation. 3. Calculate CT every day that the treatment plant is in operation 4. Complete a tracer study to determine minimum disinfection contact time, under peak demand and minimum storage conditions. 5. Representative samples of filter effluent need to be taken directly after the filters, prior to the clearwell, so that filtration performance may be accurately assessed without the influence of additional settling through storage. 6. Conduct turbidity profiles (measuring the filtered turbidity at regular intervals during filter-to-waste, following a backwash) at least quarterly 7. Change the pH sampling location to determine the required CT for disinfection, from raw water pH to first user pH at the treatment plant 8. Secure a certified treatment plant operator that meets the requirements of the system
Sanitary Survey, Finished (SNSV) 10/02/2008 3 YR  * 10/15/2008 (13) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/02/2008 6 MN 04/02/2009 10/15/2008 (13) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 08/13/2002 3 YR  * DWP Show details