OHA Drinking Water Services
PWS ID: 00157 ---- CANBY UTILITY

Most Recent Water System Survey
Survey Date: Apr 30, 2019
Notification Date: May 31, 2019 (31 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Management & Operations Bypass around hydraulic flocc/sediment unit clearwell potential path for untreated water to enter, UV intensity below min setpoint for disenfectJun 30, 2022 * Overdue
Management & Operations Major modifications not approved (plan review)Jun 30, 2022 * Overdue
Other Bypass around clearwell a potential pathway for untreated water to enter distributionJun 30, 2022 * Overdue
Disinfection No means to adequately determine disinfection contact time under peak flow and minimum storage conditionsJul 19, 2019 Jul 19, 2019
UV Disinfection No intensity sensor with alarm or shut-offJul 19, 2019 Jul 19, 2019
* Corrective Action Plan has been submitted for this deficiency.


 Show Site Visit History




For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3879