Deficiencies:
Category Deficiency Due Date Resolved Date
Management & Operations No operations and maintenance manualFeb 14, 2023 Overdue


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 11/09/2022 3 YR  * 12/27/2022 (48) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 11/09/2022 3 YR 11/09/2025 12/27/2022 (48) REGION 1 No details
Sanitary Survey, Finished (SNSV) 10/09/2019 3 YR  * 02/28/2020 (142) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 10/09/2019 3 YR 10/09/2022 02/28/2020 (142) REGION 1 No details
Sanitary Survey, Finished (SNSV) 11/03/2016 3 YR  * 11/28/2016 (25) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 11/03/2016 3 YR 11/03/2019 11/28/2016 (25) REGION 1 No details
Sanitary Survey, Finished (SNSV) 07/18/2013 3 YR  * 08/22/2013 (35) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 07/18/2013 3 YR 07/18/2016 08/22/2013 (35) REGION 1 Show details
Water Treatment Plant Site Visit (TRTP) 01/05/2012 3 YR 01/05/2015 01/19/2012 (14) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 11/04/2010 3 YR  * 12/10/2010 (36) REGION 1 Hide details
  Comments:
Source: 1. Seal the electrical conduit at the Miller Road well #2 wellhead to ensure the sanitary seal is watertight. 2. Seal the open plug to the wellhead at Miller Road Well #1 to make sure the wellhead is watertight. 3. Make sure the vent on the Dutch Canyon Well is screened properly. Treatment: 4. Monitor combined filtered effluent turbidity by reporting maximum of each individual surface water filter for compliance with SWTRule. 5. Perform turbidity profiles quarterly after a backwash. Disinfection: 6. Measure and record chlorine residual levels twice a week in the distribution. 7. Need to accurately determine contact time through Keys Road 1 MG reservoir through a tracer study. Storage: 8. Keys Zone 1 MG and High Zone 0.3 MG reservoirs need flap valve or screen on outlet. Monitoring: 9. Monitor raw Total Organic Carbon quarterly from Keys Plant to maintain reduction in DBP monitoring.
Category Deficiency Due Date Resolved Date
Finished Water Storage No flap valve, screen, or equivalent on overflowNot tracked
Monitoring & Reporting Monitoring not currentNot tracked
Well Construction Sanitary seal and casing not watertightNot tracked
Well Construction No screen on existing well ventNot tracked
Disinfection Chlorine not measured & recorded as requiredNot tracked
Disinfection No means to adequately determine disinfection contact time under peak flow and minimum storage conditionsNot tracked
Surface Water Treatment Incorrect location for compliance turbidity monitoringNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Water Treatment Plant Site Visit (TRTP) 11/04/2010 1 YR 11/04/2011 12/10/2010 (36) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 01/10/2007 3 YR  * 03/07/2007 (56) REGION 1 No details
Sanitary Survey, Finished (SNSV) 07/30/2002 3 YR  * DWP Show details
 




More information for this water system: SDWIS ID 3908
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login