| Deficiencies: |
| Category |
Deficiency |
Due Date |
Resolved Date |
| Finished Water Storage |
No flap valve, screen, or equivalent on overflow | Feb 17, 2026 |
|
| Operator Certification |
No protocol for under-certified operator | Feb 17, 2026 |
|
| Treatment |
No physical separation between treated and untreated water | Feb 17, 2026 |
|
| Surface Water Treatment |
Incorrect location for compliance turbidity monitoring | Feb 17, 2026 |
|
| Surface Water Treatment |
For conventional or direct filtration: No alarm or plant shut off for high turbidity | Feb 17, 2026 |
|
| Surface Water Treatment |
For conventional or direct filtration: Turbidity profile not conducted on individual filters at least quarterly | Feb 17, 2026 |
|
| Disinfection |
Chlorine not measured & recorded as required | Feb 17, 2026 |
Dec 04, 2025
|
| Surface Water Treatment |
For conventional filtration: Settled water not measured daily | Feb 17, 2026 |
Jan 06, 2026
|