OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00805
PWS Name: EVERGREEN ACRES
 
Who Was Contacted: Tony Cavin
Contact Phone: 971-320-0249
Contact Date: 10/26/2022
Contacted By: REILEY, MEREDITH (CLATSOP COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: EH spoke to Tony today as follow up to email re next steps to manage coliform alert response and boil notice system wide. Tony advised of the following:
• Until confirmation samples are clear of coliform, stay on boil notice.
• Crank up the chlorinator: Residual appears really low. Let’s get up to 2-3 ppm for a couple of days.
• Ask folks to keep flushing toilets and running water to get movement through the lines.
• Once chlorine has had a chance to do its job, collect at least 2 samples in different, representative points in the distribution system. Label them as “special” rather than repeat or routine.
• Triggered (source) sample: If there is a sample tap at the well, please draw from there. If not, pre-chlorinator in the pumphouse will do.

EH to follow up when results are available.

Level 2 investigation is scheduled for November 4.

UPDATE NOV 5: Operator unavailable for meeting. Will reschedule. Severe weather day contributes to delay.

 
Associated Alerts: TCR-60 - 01/12/2023 - COLIFORM (TCR)   See also: 01/20/2023, 01/24/2023, 03/01/2023, 03/10/2023

COLI22744 - 10/19/2022 - COLIFORM (TCR)   See also: 10/20/2022, 10/19/2022

COLI22725 - 10/13/2022 - COLIFORM (TCR) , E. COLI  See also: 10/13/2022, 10/19/2022



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3789