OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00657
PWS Name: PORTLAND WATER BUREAU
 
Who Was Contacted: Scott Bradway
Contact Phone: (Email address hidden)
Contact Date: 04/08/2025
Contacted By: GENTRY, CARRIE (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: Portland had a total coliform positive result from a routine coliform sample collected at sample point WQS0003 - SE 72nd and SE Harrison Street. All water quality parameters were normal - residual was 1.98 mg/L and turbidity was 0.49 NTU.

Repeat samples were collected and results will be available on April 9, 2025. No further action is required at this time.

Update:

14 other samples taken on the date of the original total coliform sample in the same general area were total coliform negative and had chlorine residuals ranging from 1.59 to 2.11 mg/L with turbidities between 0.34 and 0.84 NTU. The sample locations also included one sample from the outlet of Powell Butte.

Repeat sample at the same location was E. coli positive and samples upstream and downstream were negative for coliform. The total coliform positive sample and repeat sample from sample point WQS0003 were invalidated under OAR 333-061-0036(6)(a)(F).

Portland will take the sample station out of service until they investigate and resolve the issue. Since the original total coliform positive sample has been invalidated, it will not count towards the required number of monthly distribution samples. Other than investigating the sample station to determine why it was showing coliform presence, no further action is required at this time.
 
Associated Alerts: TCR-3700 - 04/08/2025 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3900
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Main menu:
Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login