OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00657
PWS Name: PORTLAND WATER BUREAU
 
Who Was Contacted and Phone: Elloise Eckles (503) 823-7598
Contact Date: 10/22/2009
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: TC+ response DETAILS: Elloise called to say that the outlet of Reservoir 3 was TC+ FC-. Another sample taken ( a repeat from another positive) was TC-. Repeats will be taken the morning of the 23rd. Also, the outlet of Reservoir #6 (open reservoir on mt tabor) was EC+ prior to booster chlorination. I asked if they normally boost the chlorine and she said yes. They take a sample at the outlet after booster chlorination every day. The pre-booster sample 10/19 was EC+, and the repeat 10/20 was also EC+. The inlet to the reservoir was TC-, as was the post-booster sample. We discussed that this is the reason they are required to cover the reservoirs, and we know that this exact situation could be occurring at any given time, regardless of the sample results. Since they are not providing full treatment (just residual maintenance, no contact time), this is always a public health risk. Since it is nothing new, we do not require any specific measures be taken, but recommend keeping the reservoirs clean, maintaining a chlorine residual, and sampling the post-booster chlorination water. ACTION NEEDED: none
 
Associated Alerts: COLI6993 - 10/23/2009 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3900
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login