OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00657
PWS Name: PORTLAND WATER BUREAU
 
Who Was Contacted and Phone: Yone Akagi (503) 823-7648
Contact Date: 04/20/2010
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Ecoli + response - open reservoir DETAILS: While at a Risk Communication seminar, Chris Wanner informed me that a routine coliform sample taken from the outlet of uncovered Reservoir 1 on Mt Tabor, showed a presence of Ecoli. The sample was taken Monday morning, 4/19, with a total chlorine residual of 1.4 ppm. As per their new protocol, a downstream sample had been taken at the same time, and it was negative for total coliform. Tuesday morning, routine samples were again taken from the reservoir outlet and the same downstream sample site. Results from Monday’s test came back today around 11:30 am. The reservoir was then taken off-line as per their new protocol, to reduce possible exposure. We discussed repeat sampling. Rather than do an upstream location (since it is different water quality), we talked about using modeling results to determine where the Res 1 water went, and take repeat sample from that area. Later it was determined that the Res 1 water went down Division and into downtown. They do not have sample stations in that area, so 4 samples were collected from Benson bubblers, and 1 from a regulating valve. A sample was also taken upstream of Res 1, as well as an additional repeat sample at another downstream location from Res 1, though the water likely does not represent water that came from Res 1. Portland staff are beginning to work on notification in the event that a boil water advisory is necessary. ACTION NEEDED: 4/21 all re-samples came back absent for coliform. No further action needed at this time. Yone and I will talk about how their sampling plan could be improved.
 
Associated Alerts: COLI7544 - 04/20/2010 - COLIFORM (TCR) , E. COLI

COLI7544 - 04/20/2010 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3900
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login