OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 06049 | ||
PWS Name: | SOUTHVIEW IMPROVEMENT DIST | ||
Who Was Contacted: | Wayne Niederjohn | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 04/07/2021 | ||
Contacted By: | MACPHERSON, JAMES (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform |
||
Details: | Southview wrote "We have replaced the missing screen in the vent at the top of our reservoir, disconnected a pressure tank whose bladder exhibited low pressure (7 psi), eliminated a faulty booster pump that contained a black slimy substance, disconnected our suspicious sampling stations with swivel joints, implemented and completed our cross connection prevention program during 2020, we instituted temporary residual chlorination in November for 5 days achieving 1.3 ppm chlorine throughout our distribution system, and changed our flushing procedure to reduce flow to 85 gallons per minute during flushing so as not to drop system pressures below 20 psi at our booster station during flushing." Thus, residual maintenance is not currently required as the cause of past TC+ may be addressed. If TC+ recurs in 2021, residual maintenance is required. |
||
Associated Alerts: | COLI20772 - 01/25/2021 - COLIFORM (TCR) See also: 01/25/2021 COLI20764 - 01/20/2021 - COLIFORM (TCR) See also: 01/20/2021 COLI20699 - 12/28/2020 - COLIFORM (TCR) See also: 12/28/2020 COLI20688 - 12/22/2020 - COLIFORM (TCR) See also: 12/22/2020 COLI20542 - 11/12/2020 - COLIFORM (TCR) See also: 11/17/2020 COLI20526 - 11/09/2020 - COLIFORM (TCR) See also: 11/10/2020 COLI20398 - 10/09/2020 - COLIFORM (TCR) See also: 10/12/2020, 10/13/2020 COLI20378 - 10/08/2020 - COLIFORM (TCR) See also: 10/08/2020 |