OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00100
PWS Name: BEND WATER DEPARTMENT
 
Who Was Contacted and Phone: Steve Prazak (541) 322-6349
Contact Date: 12/11/2009
Contacted By: GOSS, BILL (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
N/A
 
Details: SUMMARY: Turbidity Event Consultation DETAILS: Steve Prazak and Art Easton called to consult on a turbidity event. Late Thursday afternoon raw water turbidity peaked at 1.04 for about 30 minutes. Art suspected ice crystal formation may have raised the turbidity reading. A raw sample was collected for enumeration, but was not run by the lab due to exceeding the eight hour holding time. Discussed with Steve and Art that the 1 NTU standard is not exceeded until the turbidity reaches 1.49 NTU due to rounding, so the raw water sample was not required. ACTION NEEDED: PWS to revise SOPs to ensure all required water samples are run by the lab.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3878