OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 94489
PWS Name: WHALESHEAD BEACH RESORT, LLC
 
Who Was Contacted and Phone: Vic Lindsay (541) 469-7446
Contact Date: 06/14/2017
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: MPA Test DETAILS: MPA testing was conducted between October 31st and November 1st, by Civil West Engineering technician Jared Sylvester. The testing apparatus was connected to the spigot inside the pumphouse. The spigot is in a tee connected to the 2” PVC pipe that feeds the holding tanks uphill from the pump house. The pump was in continuous operation for the duration of the testing. The filter apparatus ball valve was manually adjusted, and bucket tested to allow for approximately .85 gpm, and a pressure of 10psi. The testing began at 1:15pm, 10-31-17.At 10:25am the following morning, the testing was discontinued, and filter collected. The total flow over 21 hours and 10 minutes was 1,129.9 gallons, for an average flow of .89 gpm. The filter was discolored due to high iron content, but flow rate remained consistent, per a second bucket test on day two, prior to discontinuing the test.The sample was packaged with ice and shipped via UPS overnight to Analytics Laboratories Inc. of Boise ID.The MPA test results were emailed to Jared Sylvester at Civil West Engineering Services 11-17-17, and then forwarded to Shawn Stevenson of the Oregon Health Authority. ACTION NEEDED: Additional testing will be conducted per OHA requirements, date and time TBD.


More information for this water system: SDWIS ID 1791
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login