OHA Drinking Water Services
OR41
PWS ID: 00657 ---- PORTLAND WATER BUREAU

Most Recent Water System Survey
Survey Date: Dec 13, 2023
Notification Date: Jan 26, 2024 (44 days)
Regulating Agency: DWS (REGION 1)
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
No deficiencies were identified.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 12/13/2023 3 YR  * 01/26/2024 (44) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 11/19/2020 3 YR  * 11/25/2020 (6) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 06/20/2017 3 YR  * 04/19/2018 (303) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 06/04/2014 3 YR  * 03/06/2015 (275) REGION 1 Show details
Watershed Evaluation (WSHD) 08/20/2013 1 YR 08/20/2014 12/27/2013 (129) REGION 1 No details
Sanitary Survey, Finished (SNSV) 04/18/2011 3 YR  * 06/27/2012 (436) DWP Hide details
  Comments:
1. The east hatch at the Arlington Heights Reservoir #1 must be watertight with curbing and an overlapping lid. Also, the tank seems to be lacking an air vent, which could be problematic. 2. Penridge tank is not inspected, so operator was not aware of screening on vent, condition of the hatch, or if the overflow had a flap valve. If the tank is to remain in service, these items must be inspected regularly. 3. Vent screens on the Powell Butte tanks #2 must be repaired. Vent screens on Powell Butte tank #1 (7 million gallon tank) have a shield over them, making it difficult to inspect, though holes in the screens were found in at least one. Consider another system that would allow for more frequent inspection of the condition of the screens. 4. Powell Butte reservoir’s north cell access had water dripping into the reservoir on the date of inspection. This must be made watertight. 5. We have no record of plan review for the Whitwood Upper and Saltzman tanks. Burlingame tanks were rehabbed in 2010 without plan review. Plan review must be submitted for these projects.
This site visit has not been entered into the deficiency database.

Watershed Evaluation (WSHD) 08/25/2009 1 YR 08/25/2010 09/21/2009 (27) REGION 1 No details
Sanitary Survey, Finished (SNSV) 11/08/2007 3 YR  * 03/13/2008 (126) REGION 1 No details
Watershed Evaluation (WSHD) 08/02/2007 1 YR 08/02/2008 01/16/2008 (167) DWP No details
Sanitary Survey, Finished (SNSV) 09/21/2004 3 YR  * DWP Show details
 




More information for this water system: SDWIS ID 3900
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules