OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00982
PWS Name: DEER ISLAND VILLAGE MHP
 
Who Was Contacted: Allison, Blueflag Realty
Contact Phone: 503-374-3956
Contact Date: 05/26/2022
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Other
Coliform
 
Details: I received a call from Allison with Blueflag Realty, the property management company for Deer Island Village MHP. Allison asked me for specifics about the sampling requirements in response to Well #1's e. coli positive result and the system's Boil Water Notice.
I stated that 5 confirmation samples at Well #1, and at least 1 distribution sample, labeled "special", are required. I also added that the State and I are requesting that a "assessment" source sample also be re-collected at Well #2, prior to any treatment/chlorination, as the original Well #2 assessment sample had a chlorine residual, and therefore may not have been collected at the raw source pre-treatment tap.
Allison said that they are taking care of the sampling, and obtained the proper bottles; she added that someone is planning to go to collect the samples and deliver them to the lab today.
I added that when all those samples test negative for total coliform (and e. coli, obviously), then Deer Island Village MHP may lift their Boil Water Notice.
 
Associated Alerts: COLI22130 - 05/24/2022 - COLIFORM (TCR) , E. COLI  See also: 05/24/2022, 05/25/2022, 05/25/2022, 05/25/2022, 05/26/2022, 05/26/2022



More information for this water system: SDWIS ID 3491
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login