OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 01174 | ||
PWS Name: | BUELL-RED PRAIRIE WD | ||
Who Was Contacted: | Brandon Ford | ||
Contact Phone: | 503-843-2885 (Email address hidden) | ||
Contact Date: | 08/28/2025 | ||
Contacted By: | HOFELD, EVAN (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | VIOLATION RESPONSE | ||
Reasons: | Operations |
||
Details: | 8-28-25 Update – I received the public notice distributed 7-9-25 for Buell Red Prairie Water District (00174). The notice covers violations for not meeting direct integrity testing requirements acquired in May and June 2025. Brandon said that WesTech restored the LRV programming as approved and sent a new SCADA screen showed both filter units passing the DIT. UF Bank 1 had an LRV of 4.219-log, PDR of 0.025 psi/min and an AVG TMP of 19.27 psi. UF Bank 2 had an LRV of 4.355-log, PDR of 0.033 psi/min and Avg TMP of 6.28 psi. 9-2-25 – Brandon sent a copy of the public notice for not meeting DIT parameters May – Aug 24, 2025. Repairs to fix the air leaks were completed and both filter units began passing the DIT on August 24, 2025. |
||
Associated Violations: | Viol #901543659, 07/01/2025 - 07/31/2025: SWTR - Failure to meet filter performance standard See also: 07/23/2025, 07/10/2025 Viol #901543654, 06/01/2025 - 06/30/2025: SWTR - Failure to meet filter performance standard See also: 07/23/2025, 07/10/2025 Viol #901543658, 06/01/2025 - 06/30/2025: SWTR - Monthly SW Report - Late/Nonreporting Viol #901543653, 05/01/2025 - 05/31/2025: SWTR - Failure to meet filter performance standard See also: 07/23/2025, 07/10/2025, 06/30/2025, 06/25/2025, 06/16/2025, 06/05/2025, 05/30/2025 |